Type High Pressure Water Mist Nozzles- Open Type

Spray Characteristics
Spray pattern: Full Cone
Spray angles: 120°(other angles optional)
Operating pressure:10~14Mpa
Strainer: 40 mesh, 120 mesh, 200 mesh
Class, I water mist: Dv0.5≤100μ, Dv0.99<200μ
K-factors of open type: 0.17, 0.45, 0.95, 1.34, 2.04, 1.19, 1.87.
K-factors of closed type: 1.25, 1.68, 2.04, others can be customized.
Contact Us Info
We manufacture and sell different types of nozzles with factory prices, high quality and fast delivery.
Our business types: retail, wholesale, customized, OEM, etc.Welcome to consult.
For any kind of query, contact us like price,delivery,sizes,MOQ,Customized etc.

  • Description
  • Nozzle parameter data
  • Quote Form
Point-blank high pressure fine water mist nozzle
Direct injection high pressure water spray nozzle adopts 3/4 or 1-1/4 bpst internal thread design, can be installed in different disinfection nozzle. The working pressure is set to 10-14mpa. The system is linked with the automatic alarm system. Sensitive response, stable flow, uniform water mist, convenient maintenance, excellent fire suppression characteristics and cost-effective.

Design features

Make and test in strict accordance with the relevant standards of water mist.
The nozzle has a unique design of direct spray type two-stage atomization structure, can produce Dv0.99≤200 micron water mist.
Spray speed, uniform distribution, strong penetration.
Very compact structure, beautiful appearance.

No deformation, no burr, high roundness, high precision, good aperture consistency.
Aperture processing range: 0.05~ 3.0mm (0.05, 0.06, 0.07, 0.08, 0.09, 0.1,0.2, 0.3,
0.4, 0.5, 1.0, 2.0, 3.0)
Support special custom aperture specifications: such as 0.11, 0.12, 0.13, 0.14, 0.16, 0.17, 0.18 MM, etc.
Pore wall roughness: 0.6um, 0.8um, 1.0um, 1.6um, 2.0um, 3.2um.
Accuracy: soil 0.002MM, soil 0.003MM, soil 0.005MM, soil 0.01MM, soil 0.02MM, soil 0.05MM.

Flow coefficient (K) Working pressure (Mpa) Working flow (L/min) Maximum installation spacing (m) Maximum installation height (m)
0.5 10.0-14.0 5.0-5.9 3 5
0.7 10.0-14.0 7.0-8.3 3 8
0.9 10.0-14.0 9.0-10.6 3 8
1 10.0-14.0 10.0-11.8 3 8
1.2 10.0-14.0 12.0-14.2 3.5 10
1.5 10.0-14.0 15.0-17.7 3.5 10
1.7 10.0-14.0 17.0-20.1 3.5 10
2 10.0-14.0 20.0-23.7 4 10
2.5 5.0-10.0 12.5-29.6 4 10
3 5.0-10.0 15.0-35.5 4 10